PVC INSULATED SINGLE CORE BUILDING WIRES

Designation: H05V-U, H07V-U, H07V-R

Standard: TS 9758 HD 21.3 S3

Anma Gerilimi: 300/500 V - 450/750 V

Construction:

  • Solid or stranded.
  • Copper conductor.
  • PVC insulation.

 

 

Application:
In dry locations, for lightining and distribution installations in conduits on or in and uder plaster and closed installation ducts.

Permisable Operating Temperature: 70°C

H05V-U, H07V-U, H07V-R
Nominal Cross-Section Construction App. Overall Diameter App.Net Weight Standart Length Standart Packing & Reel Size  Conductor D.C. Resistance Max. at 20°C   Current Carrying Capacity In Conduit In Air
mm2 mm mm kg/km m cm ohm / km A A
1 1x1,13 2,5 14 100 Kangal 18,1 11 19
1,5 1x1,38 2,7 19 100 " 12,1 15 24
2,5 1x1,78 3,3 30 100 " 7,41 20 32
4 1x2,26 4 47 100 " 4,61 25 42
6 1x2,78 4,5 67 100 " 3,08 33 54
10 7x1,35 6,2 119 100 " 1,83 45 73
16 7x1,70 7 177 100 " 1,15 61 98
25 7x2,13 9 270 100 " 0,727 83 129
35 7x2,52 10 370 100 " 0,524 103 158
50 19x1,83 12 514 1000 80 0,387 132 198
70 19x2,16 13,7 695 1000 80 0,268 165 245
95 19x2,52 15,8 960 1000 100 0,193 197 292
120 37x2,03 17,5 1200 1000 100 0,153 235 344
150 37x2,27 20 1450 1000 120 0,124 - 391
185 37x2,52 22 1800 1000 120 0,0991 - 448
240 61x2,25 25 2400 1000 140 0,0754 - 528
300 61x2,52 27 3000 1000 140 0,0601  -  608
400 61x2,85 30 3790 1000 160 0,047 - 726
500 61x3,20 33 5000 1000 180 0,0366 - 830

Print